wet chemical extinguishers FEATURES • welded stainless steel cyl inder. • chrome plated brass valve body. • stainless steel handle & lever. • pressurised with standard chuck. • control led on/off discharge. • manufactured to Austral ian Standard 1841.3. APPLICATIONS • A Class Fires (those involving paper, wood texti les etc). • F Class Fires (those involving cooking oi ls and fats). INSPECTION & MAINTENANCE Should be done every six months with Austral ian Standard 1851. CODE CAPACITY RATING OPERATING DISCHARGE OVERALL DIMENSIONS PRESSURE TIME MASS FE35WC 3.5 litre 1A4F 690kpa 33sec 7.0kg 535mm (h), 575 (diam) FE70WC 7.0 litre 2A4F 690kpa 81sec 11.9kg 630mm (h), 575mm (diam) AB:E dry powder extinguishers FEATURES • rugged epoxy coated al l steel cyl inders, resist corrosion, dents and punctures. • chrome plated brass valve body. • stainless steel handle and lever. • stainless steel hose retaining cl ip and band. • rugged epoxy coated metal vehicle type bracket on 1.0kg model. APPLICATIONS • A Class Fires (paper, wood, texti les etc). • B Class Fires (flammable l iquid fires such as oi ls, paints and solvents). • C Class Fires (flammable gas fires). • E Class Fires (energised electrical fires such as switchboards and electrical motors). INSPECTION & MAINTENANCE Should be done every six months with Austral ian Standard 1851. CODE CAPACITY RATING OPERATING DISCHARGE OVERALL DIMENSIONS PRESSURE TIME MASS FE01ABE 1.0kg 1A10B:E 1000kpa 10sec 2.0kg 300mm (h), 95mm (diam) FE25ABE 2.5kg 2A40B:E 1000kpa 14sec 4.2kg 400mm (h), 120mm (diam) FE45ABE 4.5kg 4A60B:E 1500kpa 19sec 7.2kg 480mm (h), 145mm (diam) FE90ABE 9.0kg 6A80B:E 1500kpa 24sec 13.26kg 650mm (h), 175mm (diam) fire signs & equipment 52 www.uniformsafetysigns.com