Appendix 8 Volume Three Pellet (Conversions) PM Emission Rate Indicative Heat Chimney Height 10 g/h r Output Metr es 8 40kW 7.0 20 100kW 9.5 40 200kW 10.5 60 300kW 11.5 80 400kW 12.0 100 500kW 13.0 152 700kW 14.0 253 1MW 16.0 Pellet (Custom) PM Emission Rate Indicative Heat Chimney Height 10 g/h r Output Metr es 8 100kW 7.0 15 200kW 9.5 23 300kW 9.5 30 400kW 10.5 38 500kW 10.5 63 700kW 11.5 75 1.0MW 12.0 98 1.3MW 13.0 * chimney height requirement to be assessed through resource consent process. Table 2: Chimney Height Schedules for Light Fuel Oil (LFO), Heavy Fuel Oil (HFO) and LPG LFO SO Emission Rate Indicative Heat Chimney Height 2 g/h r Output Metr es 179 40kW 12.0 448 100kW >12.0* 896 200kW >12.0* 2240 500kW >12.0* HFO SO Emission Rate Indicative Heat Chimney Height 2 g/h r Output Metr es 259 40kW >12.0* 649 100kW >12.0* 1297 200kW >12.0* 3243 500kW >12.0* App 8 - 4