Volume Three Appendix 8 LPG NO Emission Rate Indicative Heat Chimney Height 2 g/h r Output Metr es 30 100kW 6.0 75 250kW 6.5 151 500kW 8.0 225 750kW 9.0 302 1.0MW 10.0 605 2.0MW 12.0 907 3.0MW 12.0 1209 4.0MW 12.0 1512 5.0MW 12.0 2116 7.5MW 12.0 3023 10.0MW 12.0 * chimney height requirement to be assessed through resource consent process. App 8 - 5